V7.00
24905_EDEBDA0272-5019-1_EN
66
System operationSystem operation
Cos-phi curve as a function of cos-phi (P) (VDE)
0,90
0,92
0,94
1,00
0,98
0,96
P1 (0%/1,0)
P3 (55%/0,984)
P2 (50%/1,0)
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%0%
P4 (85%/0,900)
Cosphi(P)-Beispielkennlinie
Cosphi(P) characteristic curve
Cosphi
P5 (100%/0,900)
P+
untererregt
under-exited
(induktiv
inductiv
Q-Control:
The following modes can be selected:
DI 3 Q/P
rated
(change by digital input)
AI 3 Q/P
rated
(change by analog input)
U 3 Q/P
rated
(change by voltage curve)
P 3 Q/P
rated
(change by active power curve)
o The function is deactivated, i.e. the device is working with the value programmed
as target cosine1
Parameters:
Q parameters
Q-Control Yes/No
P rated 100.0 kW
Target Q
Q/Pn1 power consumption 0.00 capacitive/inductive
Q/Pn2 energy recovery 0.00 capacitive/inductive
Q/Pn3 Alarm 0.00 capacitive/inductive