System operationSystem operation
When an analogue stage is activated, then you can congure the switching hysteresis [%]
and the target [%] of the analogue stage in the menu extras => settings => system =>
parameters => switching hysteresis => Ana.=> analogue parameters.
Example:
Stage power = 50 kvar
Switching hysteresis 5% (of 50 kVAR)
Target 50% (of 50 kVAR)
the result is the following:
The switching hysteresis is 2.5 kVAR, from this missing compensation power, the ana-
logue stage begins to compensate.
The target is 25 kVar, i.e. where a large amount of compensation power is missing, a pre-
programmed stage is activated and the analogue stage takes over the residual compen-
sation.
The target is relevant if a further switching stage is accessed (the analogue stage must
then be able to work in both directions (capacitive and inductive) to balance out possible
under or overcompensation).
NOTE
SecureC does not work if an analogue stage is activated.