V7.00
24905_EDEBDA0272-5019-1_EN
92
NOTE
Now several stages can be switched simultaneously in one switch time, if the stage power
of a stage is insucient.
Example:
Settings: Qmax/Step = 20 kVar
The following can be switched at the same time:
• Stage 1 5 kVar
• Stage 2 5 kVar
• Stage 3 10 kVar
Activation takes place via: Menu extras => settings => system => parameters =>
switching performance => switching hysteresis => Qmax/Step (if the value entered is
bigger than 0, then the function is activated).
SecureC does not work if several stages are switched in one switch time.