D3DA3xx/xConnectionsandwiring
ProjectengineeringmanualV1.00
70
©KEBA
6.12 Operationonspecialsystems
TNandTTsystem
Caution
Operationisonlypermittedif:
Inthecaseofthreephasedeviceswithexternalconductorvoltages3x
230VAC,3x400VAC,3x480VACthestarpointofthesupplysystem
isearthedandthesupplysystemconformstothemaximumovervoltage
categoryIIIasperEN6180051atasystemvoltage(externalconduc
tor→starpoint)ofmaximum277V.
Atexternalconductorvoltages3x230VAC,3x400VAC,3x480VAC
Thestarpointofthesupplysystemisearthed
ThesupplysystemconformstothemaximumovervoltagecategoryIIIas
perEN6180051atasystemvoltage(externalconductor>starpoint)
ofmaximum277V.
ITsystem
Caution
Operationisnotpermitted!
Incaseofanearthfaulttheelectricalstressisapprox.twiceashigh.Clear
ancesandcreepagestoEN6180051arenolongermaintained.Thede
vicemaybedestroyedintheprocess.
6.13 DIPSwitch(SADR)
TheDIPSwithSADRislocatedonthebottomsideofthemoduleand
servesforconfigurationofthesafetyfunctionsoftheD3DA3xx/x.Formore
detailssee8Safetyfunctions.