D3DA3xx/xSafetyfunctions
ProjectengineeringmanualV1.00
80
©KEBA
8.4.3 Example:STOandSBCcontrolvialightgrid
ThecontrolofSTO1isdoneviaasafetylightgridwithOSSDoutputs.The
resetbuttonreleasesafterleavingthedangerarea(start/restartinterlock)
Illustration848:STOcontrolvialightgrid
1 ...Lightgrid 2 ...D3DA3xx/x
Information
ShortcircuitsontheOSSDoutputsto24Vanotheroutputsmustbe
detectedfromthelightgridviadiagnosismeasurementsandthen
changedintosafestate.
Thefailure"Simultaneousshortcircuitofbothoutputsto24V"mustbe
excludedbysuitablewiring!
8.4.4 Example:STOandSBCcontroldirectlyviasupplymodule
ItisforexamplepossibletocontrolthesafetyfunctionsSTOandSBCvia
safetydoor,withoutusingthesafetycontrol.Thereforethedoorswitchmust
besuppliedviatestoutputsoftheD3DP3xx/x(torecognizecrosscircuitsin
theinputcircuit).Thecrosscircuittestmustbeconfiguredsuitableviathe
DIPswitch.
Information
Itisrecommendedtouseasafetycontrolandusepreferedoneofthe
abovementionedconnectionexamples!