Configuration
August 2007 3-4 P/N 06-236716-001
04 Application Mode -
Release Circuit 2
1 — Release Circuit 2 not in use (see note 1)
2 — Manual Release or Single Zone input from DET 1
3 — Manual Release or Single Zone input from DET 2
4 — Manual Release or Single Zone input from any one of
DET 1 or DET 2
5 — Manual Release or Cross Zone input from DET 1 and
DET 2
6 — Manual Release or Cross Zone input from any two of
the following: DET 1, DET 2 and DET 3/WF
7 — Manual Release or Cross Zone input from any two of
the following: DET 1, DET 2, and SUPV 1
8 — Manual Release or Cross Zone input from any two of
the following: DET 1, DET 2, DET 3/WF, and SUPV 1 (except
DET 3/WF and SUP 1)
9 — Manual Release or Cross Zone input from SUPV 1 and
either DET 1 or DET2
6
05 Abort Both or Release
Circuit 1
1 — Activation aborts ARC 1 and ARC 2
2 — Activation aborts ARC 1 only
1
06 Abort 1 — Mode 1 (UL)
2 — Mode 2, (Reset)
3 — Mode 3 (IRI)
4 — Mode 4 (NYC)
5 — Mode 0 (Disable the Abort)
1
07 Input Circuit 3 1 — Detector (DET 3)
2 — Waterflow with Non-Silenceable NACs (DET WF)
3 — Waterflow with Silenceable NACs (DET WF)
1
08 Programmable Relay 1 1 — General alarm (DET 1, DET 2, DET 3/WF, or Manual
Release)
2 — First Alarm (DET 1, DET 2, DET 3/WF, or Manual
Release) (see note 2)
3 — First Alarm (DET 1, DET 2, DET 3/WF, Manual Release,
or SUPV 1) (see notes 2 & 3)
4 — Agent Pre-Release Condition
5 — Agent Release Condition
6 — Manual Release Input
7 — Waterflow Input
8 — Abort Input
9 — Supervisory Input
3
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
Configuration Item Configuration (Position 3) Selection
Default
Mode