Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 101
Option
Description
Waterflow: Activates alarm events when a waterflow switch closes. Select this
zone type when the devices in the zone are only connected to waterflow
switches.
Note: Do not mix device and zone types. For example, do not place a
nonlatching supervisory device in an alarm zone. When the supervisory device
activates and an alarm event is initiated, the alarm event automatically clears
when the device restores without having to reset the panel.
Label
Enter a text label for the zone (two lines of 20 characters). When you have
finished, choose Save.
Correlation groups
Enter the number of the correlation group. Choose Yes or No.
“Yes” adds the item to the group.
“No” removes the item from the group
When you have finished, choose Save. For more information on correlation
groups, seeWhat is a correlation group?on page 37.
Event notification
Set the active, trouble, disable, prealarm, alarm verify, maintenance alert, and
test event information by choosing one and then setting the notification
information. When you have finished, choose Save. See Factory default
settingson page 42 for zone event notification default settings.
Note: If your CMS is set to zone reporting, the event notification information
sent to the receiver comes from the programming in this section.
Printer: Yes or No. This controls whether event information is sent to the
printer
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Controls whether event information is sent to the connected
network
CID: Contact ID event code (000 to 999)
To program a zone:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Loop Configuration.
4. Choose Zone and enter the zone number.
5. Program each zone in the system using Table 29 on page 100.
6. When you finish programming an option, choose Save, and then continue.
7. Press the Menu button to exit menu mode, or continue programming.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals