Chapter 3: System operation
140 P/N 3102351-EN ⢠REV 005 ⢠ISS 28DEC18
LCD Printer [1]
Zone alarm Alarm active ALRM ACT
Zone waterflow Alarm active ALRM ACT
Alarm ON Alarm active ALRM ACT
Supervisory type reporting
Input duct alarm Supervisory DUCT ACT
CO supervisory Gas CO active
Zone supervisory Supervisory SUPV ACT
Input supervisory latching Supervisory SUPV ACT
Input supervisory nonlatching Supervisory SUPV ACT
Monitor type reporting
CO monitor Gas CO active COMO ACT
Zone monitor Monitor MON ACT
Input monitor Monitor MON ACT
Outputs are latched Outputs are latched Outputs are latched
Prealarm reporting Prealarm PALM ACT
Alarm verify reporting Alarm verify ALMV ACT
Maintenance alert reporting Maint. alert MANT ACT
All devices Trouble TRBL ACT
All devices Disable DSBL ACT
All devices Test TEST ACT
[1] See āEvent printout examplesā below for an example of how events appear when printed.
Event printout examples
Event information is printed each time an event takes place provided a printer is connected to
the system. The following is an example of what the event information looks like on the printout
and a description of each piece of information printed for an event.
Annunciator event
TRBL ACT | 18:00:07 01/01/2007 A:008
Annunciator 08
Where:
TRBL ACT = Trouble event
18:00:07 01/01/2007 = Time and date the event took place
A:008 = Annunciator 08
Annunciator 08 = Label (could be the default label or a custom label)