Appendix C: Applications
P/N 3102351-EN • REV 005 • ISS 28DEC18 235
For example, if an alarm occurs on the third floor:
The Floor 3 Correlation turns on the sounders on the floor of the alarm (including those
inside dwelling units).
The Hallway Correlation turns on hallway sounders throughout the building.
The In-Suite Signal Silence Correlation turns on sounders in residences on all other floors.
After 60 seconds, the In-Suite Signal Silence Correlation, which has in-suite signal silence
enabled, silences sounders inside dwelling units on all other floors. These signals remain
off until the in-suite signal silence timer expires or a subsequent alarm comes in.