Appendix D: Device types to personality codes correlation
P/N 3102351-EN • REV 005 • ISS 28DEC18 239
Model
Device type
Personality code
CT1
Supervisory Latching
(4) Active - NO latching (Class B)
CT1
Supervisory Non
-Latching (3) Active - NO nonlatching (Class B)
CT1
Unlatch outputs
(3) Active - NO nonlatching (Class B)
CT1
Waterflow
(2) Alarm - NO delayed latching (Class B)
CT1
Waterflow No Delay
(1) Alarm - NO latching (Class B)
CT2
Alarm
(1) Alarm - NO latching (Class B)
CT2
Heat
(1) Alarm - NO latching (Class B)
CT2
Monitor
(3) Active - NO nonlatching (Class B)
CT2
Pull Station
(1) Alarm - NO latching (Class B)
CT2
Remote AC Fail
(3) Active - NO nonlatching (Class B)
CT2
Remote Drill
(3) Active - NO nonlatching (Class B)
CT2
Remote Reset
(3) Active - NO nonlatching (Class B)
CT2
Remote Signal Silence
(3) Active - NO nonlatching (Class B)
CT2
Smoke
(1) Alarm - NO latching (Class B)
CT2
Supervisory Latching
(4) Active - NO latching (Class B)
CT2
Supervisory Non
-Latching (3) Active - NO nonlatching (Class B)
CT2
Unlatch
Outputs (3) Active - NO nonlatching (Class B)
CT2
Waterflow
(2) Alarm - NO delayed latching (Class B)
CT2
Waterflow No Delay
(1) Alarm - NO latching (Class B)
DTS
Duct Alarm
(1) Alarm - NO latching (Class B)
DTS
Duct
Supervisory Latching (4) Active - NO latching (Class B)
DTS
Duct Supervisory Non
-Latching (3) Active - NO nonlatching (Class B)
HC
D
Heat Fixed + CO Alarm
(66) Fixed CO Active3 Latching
HCD
Heat Fixed + CO Monitor Latching
(66) Fixed CO Active3 Latching
HCD
Heat Fixed + CO Monitor Non
-Latching
(69) Fixed CO Active3 Nonlatching
HCD
Heat Fixed + CO Supv Latching
(66) Fixed CO Active3 Latching
HCD
Heat Fixed + CO Supv Non
-Latching (69) Fixed CO Active3 nonlatching
HCD
Heat ROR + CO Alarm
(65) ROR CO Active3 Latching
HCD
Heat ROR + CO Monitor Latching
(65) ROR CO Active3 Latching
HCD
Heat ROR + CO Monitor Non
-Latching
(68) ROR CO Active3 nonlatching
HCD
Heat ROR + CO Supv Latching
(65) ROR CO Active3 Latching
HCD
Heat ROR + CO Supv Non
-Latching (68) ROR CO Active3 nonlatching
HFS
/HFD
Heat
(1) Alarm - NO latching (Class B)
HRS
/HRD
Heat ROR
(1) Alarm - NO latching (Class B)
IM
Monitor
(1) Alarm - NO latching (Class B)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals