Chapter 2: Front panel programming
78 P/N 3102351-EN • REV 005 • ISS 28DEC18
Description
Sets the options needed for messages for the active, alarm verify, disable, maintenance,
prealarm, test, trouble, and active3 events. See “Factory default settings” on page 42 for
device event notification default settings.
Printer: Yes or No. This controls whether event information is sent to the printer.
Coder: Four-digit coded output that is played in response to alarm conditions (00-00-00-00 to
99-99-99-99).
Dialer:
• Acct 1 & 2: Event information is sent to both dialer accounts
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
NET (1-8): Yes or No. Controls whether event information is sent to the connected Ethernet
receiver.
CID: Contact ID event code (000 to 999).
When you have finished, choose Save.
The PHS/PHD operates in Operation mode (day) or Alternate (Alt) Operation mode (night).
This allows you to change the detector’s photo/heat from supervisory/alarm to alarm/alarm.
This is applicable only for “heat + supervisory smoke latching” and “heat + supervisory smoke
nonlatching” device types of the PHS/PHD.
Sets the daytime smoke level sensitivity. Choose least, less, more, normal, or most.
Sets the nighttime smoke level sensitivity. Choose least, less, more, normal, or most.
Sets the daytime prealarm percentage. Choose Off or 50, 55, 60, 65, 70, 75, 80, or 90
percent.
This sets the amount of smoke that indicates a prealarm event before an actual alarm event is
indicated. The percentage is based on the sensitivit
y level selected above. For example, if you
choose normal sensitivity and select 50 percent for your prealarm, when smoke levels reach
50% of the normal smoke level required to initiate an alarm, a prealarm event is indicated.
Sets the nighttime prealarm percentage. Choose Off or 50, 55, 60, 65, 70, 75, 80, or 90
percent.
This sets the amount of smoke that indicates a prealarm event before an actual alarm event is
indicated. The percentage is based on the sensitivity level selected above
choose normal sensitivity and select 50 percent for your prealarm, when smoke levels reach
50% of the normal smoke level required to initiate an alarm, a prealarm event is indicated.
Sets the base type for detectors. Choose standard, relay, isolator, or sounder.
This option controls the conditions that activate the relay or sounder detector base.
Note: All base follow settings except Head and Riser can be activated by correlation groups.
Note: For PS/PD, PHS/PHD, IPHS, and SD detectors configured as “Supervisory Non-
latching” device type or for PCOS/PCD detectors (smoke element) configured as “Smoke
Supervisory Non-latching” device type, if the base is Relay/Sounder, then the follow type
option cannot be configured as “Head.” The default follow type in this case is “Alarm.”
Select from the following values.