EasyManua.ls Logo

Klimor EVO -T - 11.2 First start-up

Klimor EVO -T
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
84
AUTOMATION AND CONTROL SYSTEM FOR UNITS EVO-T; EVO-T COMPACT
OPERATION AND MAINTENANCE MANUAL
10.5 Communication RS485 Slave, Modbus RTU and connection method with the EBM motor
Fig. 20 Example for “EVO-T 4S” system, with double air supply, double air exhaust
Fig. 21. Example for “EVO-T 2S” system, with single air supply, single air exhaust.
Table no. 25 Connection of the EBM fan wires
Cable Connection Cable color Cable function
1,2 PE
yellow-
-green
Ground
3 N Blue Power supply – "0"
5 L Black Power supply – Phase
6 NC White 1 Motor condition relay – open, failure
7 COM White 2 Motor condition relay – open, failure
8 0-10V Yellow Analog input
10 RSB Brown RS485 MODBUS
11 RSA White RS 485 MODBUS
12 GND Blue "0" for control signal
13 +10V Red 10VDC 10mA output
Only 1, 2, 3, 5, 6, 7, 10, 11, 12 wires are connected to appropriate terminals at the control board.

Table of Contents