EasyManua.ls Logo

Klimor EVO -T - 11. CONTROL MODULES OF EH-EVO-T ELECTRIC HEATERS; 11.1 HE electric heater control module

Klimor EVO -T
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83
10.4 Communication of the RS485 Slave, Modbus RTU with Danfoss FC51 inverter
Please see the website below in order to obtain technical documentation of Danfoss inverters.
http://www.danfoss.com/poland/businessareas/drivessolutions/frequency+converters/vlt+micro+drive.htm
Fig. 18 Example for “EVO-T 4S” system, with double air supply, double air exhaust
Fig. 19 Example for “EVO-T 2S” system, with single air supply, single air exhaust or double air supply only
Table no. 24 Danfoss FC51 inverters conguration, RS485 control
Code Name Set point value Description
1-03 Torque specs. 0 Constant torque
1-20 Rated motor output ...kW Motor rating plate
1-24 Rated motor current ...A Motor rating plate
1-25 Rated motor speed ...rpm Motor rating plate
1-90 Thermal motor protection 4 Emergency ETR only
3-02 Min requested frequency 0.000 Always enter this value
3-03 Max requested frequency Fz max Custom setting
3-17 Source of requested value 3 11 Modbus
4-14 Max. output frequency Fz max Custom setting
4-16 Output current limit 110.0
5-40 Relay function 6 Operation without alarm
8-01 Control location 0 Digital and control word
8-02 Source of control word 1 FC RS485
8-03 Communication latency time 10.0
8-04 Reaction on communication time-out 2 Stop
8-30 Selection of communication protocol 2 Modbus RTU
8-31 Inverter address in Modbus
1 Air supply fan inverter
2 Air supply fan inverter 2
3 Air exhaust fan inverter
4 Air exhaust fan inverter 2
8-32 FC port baud rate 2 9600
8-33 FC port parity 3 No parity, 2 stop bits
NOTE:
Fz max – inverter frequency for operation with max fan air ow (resulted from air distribution system adjustment). Initially enter the
frequency from the AHU technical documentation.

Table of Contents