Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019 83
Error messages
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: Invalid module configuration [0x01bc6430]
PROFINET: Record Parameter: Invalid read [0x01bc6501]
PROFINET: Record Parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
Response (Lenze setting printed in bold) Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause Remedy
A module or submodule does not comply with the confi-
guration of the Siemens S7 engineering tool.
Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Invalid parameter read access Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Invalid parameter write access
When reading back the data, the IO Controller has re-
quested a data length (number of data bytes) that is to
small.
Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
• Output data invalid.
• Connection to Siemens S7 has been interrupted.
• Check cables and terminals.
• Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold) Setting: C13880/1 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The data exchange via PROFINET has been terminated.
• Also see the chapter "Interruption of PROFINET
communication" ( 71).
• Check cables and terminals.
• Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold) Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause Remedy
Station name is not DNS-conform. Use a DNS-compliant station name.
Setting the station name
( 36)