Parameterising analog modules
Signal functions of 4xanalog input
12
Parameter setting
12.3
12.3.4
l
12.3-8
EDSPM-TXXX-3.0-04/2004
Parameter
bytes
2/3/4/5
Tolerance
2)
Format
1)
Signal rangeSignal function
0D
h
Resistance
measurement with
with
60 Ω
0 {0.01 Ω} +60.00 ±0.1 % of the final
value
0E
h
two-wire connection
with
600 Ω
0 {0.01 Ω} +600.00
A
±0.05 % of the
final value
0F
h
with
3000 Ω
0 {0.01 Ω} +3000.00 ±0.05 % of the
final value
10
h
Temperature
measurement with
with type
J
-210.0 {0.1 °C} +850.0 ±1 °C
11
h
thermoelement and
external
with type
K
-270.0 {0.1 °C} +1200.0 ±1.5 °C
12
h
compensa
ion 4
)
with type
N
-200.0 {0.1 °C} +1300.0
±1.5 °C
13
h
with type
R
-50.0 {0.1 °C} +1760.0
±4 °C
14
h
with type
T
-270.0 {0.1 °C} +400.0 ±1.5 °C
15
h
with type
S
-50.0 {0.1 °C} +1760.0 ±5 °C
18
h
Temperature
measurement with
with type
J
-210.0 {0.1 °C} +850.0 ±1.5 °C
19
h
thermoelement and
internal
with type
K
-270.0 {0.1 °C} +1200.0 ±2 °C
1A
h
compensa
ion 5
)
with type
N
-200.0 {0.1 °C} +1300.0
±2 °C
1Bh with type
R
-50.0 {0.1 °C} +1760.0
±5 °C
1C
h
with type
T
-270.0 {0.1 °C} +400.0 ±2 °C
1D
h
with type
S
-50.0 {0.1 °C} +1760.0 ±5 °C
27
h
Voltage
measurement
0...50 mV
0
0
{0.01 mV}
{1
dec
}
+50.00
27648
±0.1 % of the final
value
Lower range limit –
Upper range limit: +59.25 mV
32767
dec
28
h
Voltage
measurement
±10 V
-10.00
-27648
{0.01V}
{1
dec
}
+10.00
27648
±0.05 % of the
final value
Lower range limit: -11.85 V
-32767
dec
A
Upper range limit: +11.85 V
32767
dec
29
h
Voltage
measurement
±4 V
-4.00
-27648
{0.01V}
{1
dec
}
+4.00 V
27648
dec
±0.05 % of the
final value
Lower range limit: -4.74 V
-32767
dec
A
Upper range limit: +4.74 V
32767
dec
2A
h
Voltage
measurement
±400 mV
-400
-27648
{1 mV}
{1
dec
}
+400
27648
±0.1 % of the final
value
Lower range limit: -474 mV
-32767
dec
A
Upper range limit: +474 mV
32767
dec