Parameterising analog modules
Signal functions of 4xanalog input
12
Parameter setting
12.3
12.3.4
l
12.3-9
EDSPM-TXXX-3.0-04/2004
Parameter
bytes
2/3/4/5
Tolerance
2)
Format
1)
Signal rangeSignal function
2C
h
Current
measurement
±20 mA
-20.00
-27648
{0.01 mA}
{1
dec
}
+20.00
27648
±0.05 % of the
final value
Lower range limit: -23.70 mA
-32767
dec
A
Upper range limit: +23.70 mA
+32767
dec
2D
h
Current
measurement
4...20 mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
27648
±0.05 % of the
final value
Lower range limit: 1.185 mA
-4864
dec
A
Upper range limit: +22.96 mA
+32767
dec
32
h
Resistance
measurement with
with
6000 Ω
0
0
{0.01 Ω}
{1
dec
}
+6000.00
32767
dec
±0.05 % of the
final value
33
h
four-wire connection
with
6000 Ω
0
0
{0.01 Ω}
{1
dec
}
+6000.00
6000
dec
±0.05 % of the
final value
35
h
with
60 Ω
0
0
{0.01 Ω} +6000.00
6000
dec
±0.2 % of the final
value
3)
36
h
with
600 Ω
0
0
{0.01 Ω}
{1
dec
}
+600.00
6000
dec
±0.1 % of the final
value
3)
37
h
with
3000 Ω
0
0
{0.01 Ω}
{1
dec
}
+3000.00
30000
dec
±0.1 % of the final
value
3)
38
h
with
6000 Ω
0
0
{0.01 Ω}
{1
dec
}
+6000.00
6000
dec
±0.1 % of the final
value
3)
3A
h
Current
measurement
±20 mA
-20.00
-16384
{0.01 mA}
{1
dec
}
+20.00
16384
±0.05 % of the
final value
Lower range limit: -23.70 mA
-19456
dec
A
Upper range limit: +23.70 mA
+19456
dec
3Bh Voltage
measurement
±10 V
-10.00
-16384
{0.01V}
{1
dec
}
+10.00
16384
±0.2 % of the final
value
Lower range limit: -11.85 V
-20480
dec
A
Upper range limit: +11.85 V
20480
dec
3D
h
Resistance
measurement with
with
60 Ω
0
0
{0.01 Ω}
{1
dec
}
+60.00
6000
dec
±0.1 % of the final
value
3E
h
four-wire connection
with
600 Ω
0
0
{0.01 Ω}
{1
dec
}
+600.00
6000
dec
A
±0.05 % of the
final value
3F
h
with
3000 Ω
0
0
{0.01 Ω}
{1
dec
}
+3000.00
30000
dec
±0.05 % of the
final value
57
h
Voltage
measurement
0...50 mV
0
0
{0.01 mV}
{1
dec
}
+50.00
5000
±0.1 % of the final
value
Upper range limit: +59.25 V
5925
dec
58
h
Voltage
measurement
±10 V
-10.00
-10000
{0.01V}
{1
dec
}
+10.00
10000
±0.05 % of the
final value
Lower range limit: -11.85 V
-11850
dec
A
Upper range limit: +11.85 V
11850
dec
59
h
Voltage
measurement
±4 V
-4.00
-40000
{0.01V}
{1
dec
}
+4.00 V
40000
±0.05 % of the
final value
Lower range limit: -4.74 V
-47400
dec
A
Upper range limit: +4.74 V
47400
dec