Parameterising analog modules
Signal functions of 4xanalog input /output
12
Parameter setting
12.3
12.3.6
l
12.3-14
EDSPM-TXXX-3.0-04/2004
Parameter
bytes 2/3
Tolerance
2)
Format
1)
Signal rangeSignal function
2C
h
Current measuring ±20 mA
-20.00
-27648
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.3 % of the
final value
Lower range limit -23.51 mA
-32512
dec
A
Upper range limit: +23.51 mA
+32511
dec
2D
h
Current measuring 4 ... 20 mA
+4.00
0
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.8 % of the
final value
Lower range limit +1.18 mA
-4864
dec
A
Upper range limit: +22.81 mA
+32511
dec
7E
h
Current measuring 0 ... 20 mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.6 % of the
final value
Lower range limit -
Upper range limit: +23.52 mA
+32511
dec
FF
h
Analog input deactivated
1)
Format of the i nput data (Q 12.3-7).
2)
The tolerance values have been detected at a temperature of 25 °C and 15 conversions/s. Sensor inaccuracies
have not been considered.
Parameter
bytes 4/5
Signal function Signal range Format
1)
Tolerance
2)
00
h
Parameter data in module not overwritten
01
h
Voltage signal output ±10 V
-10.00
-16384
{0.01V}
{1
dec
}
+10.00
+16384
±0.2 % of the
final value
Lower range limit: -12.50 V
-20480
dec
B
Upper range limit: +12.50 V
+20480
dec
02
h
Voltage signal output 1 ... 5 V
+1.00
0
{0.01V}
{1
dec
}
+5.00
+16384
±0.6 % of the
final value
Lower range limit: 0.00 V
-4096
dec
B
Upper range limit: +6.00 V
+20480
dec
05
h
Voltage signal output 0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+16384
±0.4 % of the
final value
Lower range limit: -
B
Upper range limit: +12.50 V
+20480
dec
09
h
Voltage signal output ±10 V
-10.00
-27648
{0.01V}
{1
dec
}
+10.00
+27648
±0.2 % of the
final value
Lower range limit: -11.76 V
-32512
dec
A
Upper range limit: +11.76 V
+32511
dec
0A
h
Voltage signal output 1 ... 5 V
+1.00
0
{0.01V}
{1
dec
}
+5.00
+27648
±0.6 % of the
final value
Lower range limit: 0.00 V
-6912
dec
A
Upper range limit: +5.704 V
+32511
dec
Output functions