Parameterising analog modules
Signal functions of 4xanalog input /output
12
Parameter setting
12.3
12.3.6
l
12.3-15
EDSPM-TXXX-3.0-04/2004
Parameter
bytes 4/5
Tolerance
2)
Format
1)
Signal rangeSignal function
0D
h
Voltage signal output 0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+27648
±0.4 % of the
final value
Lower range limit: -
Upper range limit: +11.76 V
+32511
dec
03
h
Current signal output ±20 mA
-20.00
-16384
{0.01 mA}
{1
dec
}
+20.00
+16384
±0.3 % of the
final value
Lower range limit -25.00 mA
-20480
dec
B
Upper range limit: +25.00 mA
+20480
dec
04
h
Current signal output 4 ... 20 mA
+4.00
0
{0.01 mA}
{1
dec
}
+20.00
+16384
±0.8 % of the
final value
Lower range limit +0.00 mA
-4096
dec
B
Upper range limit: +24.00 mA
+20480
dec
06
h
Current signal output 0 ... 20 mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
+16384
±0.6 % of the
final value
Lower range limit -
B
Upper range limit: +25.00 mA
+20480
dec
0Bh Current signal output ±20 mA
-20.00
-27648
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.3 % of the
final value
Lower range limit -23.52 mA
-32512
dec
A
Upper range limit: +23.52 mA
+32511
dec
0C
h
Current signal output 4 ... 20 mA
+4.00
0
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.8 % of the
final value
Lower range limit +0.00 mA
-6912
dec
A
Upper range limit: +22.81 mA
+32511
dec
0E
h
Current signal output 0 ... 20 mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
+27648
±0.6 % of the
final value
Lower range limit -
Upper range limit: +23.52 mA
+32511
dec
FF
h
Analog output is switched off
1)
Format of the o utput data (Q 12.3-7).
2)
The tolerance values have been detected at a temperature of 25 °C and 15 conversions/s. Sensor inaccuracies
have not been considered.