Index table
14
Appendix
14.2
l
14.2-2
EDSPM-TXXX-3.0-04/2004
Index ImportantPossible settingsName
SelectionLenze
I100A
h
DIS: Software
version
Display only
Software version
I100B
h
Node ID 0 0 {1} 63 Display only
System bus node address
I100C
h
Guard time 0 0 {1 ms} 65535 Node Guarding
Monitoring time
0 = monitoring not active
E 9.7-1
I100D
h
Life time factor 0 0 {1} 255 Node Guarding
Response time computation factor
0 = monitoring not active
The response time is computed as:
Monitoring period x factor
E 9.7-1
I100E
h
Node Guarding
identifier
Display only
identifier = basic identifier + node address
(basic identifier cannot be modified)
E 9.7-1
I1010
h
Store parameter 0 Store in accordance with CANopen
(communication protocol DS301/DS401)
I1011
h
Restore parameter 0 Load factory setting in accordance with
CANopen(communication protocol
DS301/DS401)
I1014
h
COB ID emergency Emergency telegram
Identifier 80h + node address is displayed
after boot-up.
E 9.11-2
I1016
h
Heartbeat
Data contents
The I/O system IP20 can monitor up to five
E 9.8-1
consumer
ime
Heartbeat time Node ID reserved
nodes (subindex 1 ... 5).
If the monitored node does not respond,
Byte 1 Byte 2 Byte 3 Byte 4
,
the I/O system IP20 changes to the
”
-
”
00
h
00
h
00
h
00
h
re-
pera
ona
s
a
e.
eou
pu
s
switch to a defined state.
1
Heartbeat time 0 0 {1 ms} 65535
In the compact system, only the subindex 1
E 9.8-1
Node ID 0 0 {1} 255
is available
2
Heartbeat time 0 0 {1 ms} 65535
Hear
bea
ime:
Node ID 0 0 {1} 255
emon
ore
no
emus
respon
w
n
he
ime se
. The
ime is se
in b
e0and
3
Heartbeat time 0 0 {1 ms} 65535
.
1.
Node ID 0 0 {1} 255
Node ID:
4
Heartbeat time 0 0 {1 ms} 65535
Node address of the node to be monitored.
Node ID 0 0 {1} 255
ea
ress
sse
n
y
e
.
5
Heartbeat time 0 0 {1 ms} 65535
Node ID 0 0 {1} 255
I1017
h
Heartbeat producer
time
0
0 {1 ms} 65535
The I/O system IP20 can be monitored by
other nodes.
Within this time the device status of the I/O
E 9.8-1
0 Function is not active
system IP20 is transmitted to the fieldbus.
In the communication protocol, system bus
(CAN) is not available
I1018
h
Display only
1 Vendor ID
device identifier
2 Product code
3 Revision number
I1027
h
Type of
Display only E 9.11-3
1 Module no. 1
module list
2 Module no. 2
Subindices 1 ... 32 Module identifiers of
... ...
ep
ugge
mo
u
es
32 Module no. 32