Chapter 4. Installation and Wiring
For XGT Panel power supply, I / O devices and power devices, separate the power supply system as shown below.
Main
Power
Noise
Filter
HMI
power
PE
Others
Do not bring the power line of the XGT Panel close to the main circuit (high voltage, high current) line or I / O signal
line. Possible 100mm Install at an interval of more than two.
Use the surge absorber as shown in the figure below to prevent surge such as lightning.
(1) Separate grounding (E2) of the XGT Panel of ground surge absorber (E1).
(2) Select the surge absorber so that the surge absorber does not exceed the maximum allowable voltage even when
the power supply voltage rises to a maximum please give it to me.
XGT Panel
Surge absorber for preventing lightning