EN
Control CS 310 / Rev.I 1.55 – 47
Fault / error message LED indicator Remarks
ERROR MSBUS Flashes 9x Communication error between the control and the installed MS
BUS end device.
– Check the cable and socket connections and replace, if
necessary.
SERVICE Flashes 10x The programmed service interval has been reached.
– Resetorredeneserviceinterval.
➔ “10.2 Input operating mode“ / SERVICE parameter
ERROR POWERSEGM. Flashes 11x The load contactor or a relay is defective.
– The circuit board must be replaced.
ERROR SKS Continuous light
Travel only possible in deadman mode
Closing edge safety device faulty in OPENING or CLOSING
direction.
– Check the closing edge safety device and the spiral cable
and, if necessary, Check the RADIO transmission system.
ERROR LIGHT BAR Continuous light
Travel in CLOSING direction only possible in
deadman mode
The installed photocell indicates a permanent fault.
– Check photocell (function and alignment).
– Check cabling.