Installation
CAUTION:
To ensure adequate heat dissipation make sure that no objects are placed on top of the
communication server (see also Location requirements). Minimum distances must also be observed
as shown in Minimum distances on page 87.
4.3 Powering the communication server
The communication server is powered as standard with 230 VAC or 115 VAC. To ensure that its operation
is maintained even in the event of a mains outage, an external uninterruptible power supply (UPS) must be
used.
4.3.1 115/230 V power supply
The communication server is powered by the supplied power supply unit. The power supply unit is
connected to the mains using a two-pin standard power cable.
Warning:
Hazard due to heat generation in the event of short-circuits. The mains power supply connection must
be protected with 16 A maximum in countries with 230 V mains power (for instance in Europe), and
with 20 A maximum in countries with 115 V mains power (e.g. in North America).
Please also note the following points:
• The mains connector acts as a disconnecting device and must be positioned so that it is easily
accessible.
Release 7.1
System Manual for Mitel SMB Controller 94