68P80801E30-A 5/1/2002 11-3
Gen 3 Site Controller System Manual Chapter 11 Gen 2 Environmental Alarm System
EAS2 Functional Description
Performance Specications
Table 11-2 lists the EAS2 specifications.
Theory of Operation
The EAS2 provides a direct interface between the Site Controller and
various site alarms. Figure 11-2 shows a functional block diagram of the
EAS2.
The EAS2 is configured for 48 dry contact input sensors and 8 relay closure
outputs. Each I/0 provides 4000V of isolation between field wiring and
sensitive control circuitry.
Table 11-2 EAS2 Performance Specifications
Specication Value or Range
Input supply voltage
range
-41 to -60 Vdc
Power consumption Typical: 22W
Maximum: 50W
Operating temperature
range
-30° to 60° C (-22° to 140° F)
Storage temperature
range
-40° to 85° C (-40° to 185° F)
Physical dimensions:
Height
Width
1 Rack Unit (RU)
482.6 mm (19")
Humidity 75% R.H. at 55°C (Max.)
Maximum loop length 24 or 32 gauge wire => 610 m
(2000’)
Alarm input "ON"
current
5.0 mA min.
Alarm input "OFF"
current
0.1 mA max.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Motorola iDEN Site Controller and is the answer not in the manual?

Motorola iDEN Site Controller Specifications

General IconGeneral
BrandMotorola
ModeliDEN Site Controller
CategoryController
LanguageEnglish

Related product manuals