8 Operation
Maschinenfabrik Reinhausen GmbH 2018116 5252433/02 ENECOTAP
®
VPD
®
CONTROL PRO
The following parameters are available for setting function monitoring:
▪ Function monitoring
▪ Hysteresis
▪ Delay time
Figure76: Setting function monitoring
To set bandwidth monitoring, proceed as follows:
1. Go to Settings > Parameters > Bandwidth monitoring.
2. Select the desired parameter.
3. Set parameter.
4. Press the Accept button to save the modified parameter.
Function monitoring
You can use this parameter to activate function monitoring. You can select
the following options:
Setting Behavior
Off Function monitoring is deactivated.
Only Auto Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual Function monitoring is active in AVR AUTO and AVR
MANUAL operating mode
Table39: Activate function monitoring
Hysteresis limit value
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.