12 Technical data
Maschinenfabrik Reinhausen GmbH 2018 1835252433/02 EN ECOTAP
®
VPD
®
CONTROL PRO
12.6 Dimensions and weight
Dimensions (W x H x D) 470 mm x 130 mm x 110 mm (18.5 in x 5.1 in x 4.3 in)
Weight Max. 2.6 kg
Figure110: Dimensions
12.7 Ambient conditions
Operating temperature -25...+70°C
Storage temperature -40...+85°C
Relative humidity 10...95% non-condensing
Air pressure Corresponds to 2000m above sea levelCorresponds to
2000m above sea level
Minimum spacing to other
devices/control cabinet
Top/Bottom: 88.9 mm (3.5 in; corresponds to 2 RU),
back 30 mm (1.2 in)
Table80: Permissible ambient conditions
12.8 Standards and directives
Electrical safety
IEC 61010-1
IEC 61010-2-030
Safety requirements for electrical measurement and con-
trol and regulation equipment and laboratory instruments
▪ Protection class 1
▪ Overvoltage category III
▪ Contamination level 2
IEC 60950-1 Information technology equipment – Safety
Table81: Electrical safety