8 Operation
Maschinenfabrik Reinhausen GmbH 2018 1295252433/02 EN ECOTAP
®
VPD
®
CONTROL PRO
3. Press the Accept button to save the modified parameter.
Timeout confirmation
You can use this parameter to set the timeout for unsolicited messages.
To set the timeout for unsolicited messages, proceed as follows:
1. Go to Settings > Parameters > DNP3 > Timeout.
2. Enter the timeout.
3. Press the Accept button to save the modified parameter.
Timeout for response confirmation
You can use this parameter to set the timeout for response confirmation for
unsolicited messages.
To set the timeout for response confirmation, proceed as follows:
1. Go to Settings > Parameters > DNP3 > Timeout for response confir-
mation.
2. Enter the timeout.
3. Press the Accept button to save the modified parameter.
User ID code
You can use this parameter to set the user ID code.
To set the user ID code, proceed as follows:
1. Go to Settings > Parameters > DNP3 > User ID code.
2. Enter the user ID code.
3. Press the Accept button to save the modified parameter.
8.11.6 Configuring GOOSE (optional)
You can use the optional GOOSE function to send GOOSE messages
(GOOSE publisher) or receive GOOSE messages (GOOSE subscriber) via
the IEC 61850 control system protocol with the device.
The configuration of GOOSE is described in the following sections.
8.11.6.1 Importing CID/SCD file
Note the following definitions for importing a CID file or SCD file.
Only the following elements may differ between the imported IED and the
exported IED from the TEMPLATE.icd.
DataSet elements can be created in each LN
ReportControl elements can be created in the LN containing the associ-
ated DataSet
IP address (if this is not present, the preset one is used)