12 Technical data
Maschinenfabrik Reinhausen GmbH 2018 1815252433/02 EN ECOTAP
®
VPD
®
CONTROL PRO
Interface Pin Description
2 CAN-L
3 CAN-GND
7 CAN-H
Table74: CAN1, CAN2
CAN bus Terminating resistor
▪ D-SUB plug connector (9 pins)
▪ R = 120 Ω
Connector with terminal strip for directly connecting
CAN lines
Media converter for COM2
interface (only RS232)
Adapter from D-SUB (9 pins) to fiber-optic cable:
▪ ACF660/ST: F-ST, 660 nm, range max. 60 m at 40
kilobaud
▪ ACF660/SMA: F-SMA, 660 nm, range max. 60 m at
40 kilobaud
▪ ACF850/ST: F-ST, 850 nm, range max. 1000 m at
40 kilobaud
▪ ACF850/SMA: F-SMA, 850 nm, range max. 1000 m
at 40 kilobaud
Table75: Optional accessories
12.5 System networking
MC 2-2
Description Media converter
Interfaces 2x RJ45
2x duplex LC (SFP)
RJ45 Max. 100m (per section)
10/100 Mbit/s
Cable impedance 100Ω
Fiber-optic cable Max. 2,000 m
100 Mbit/s
Light-emitting diode: class 1
Wave length: 1310nm
Max. optical output power: <1 mW (in accordance
with IEC 60825-1:2014)
Table76: Technical data for the MC 2-2 assembly