4 Product description
Maschinenfabrik Reinhausen GmbH 201822 5252433/02 ENECOTAP
®
VPD
®
CONTROL PRO
4.3 Performance features
The device offers the following functions:
Automatic voltage regulation AVR pro
Measurement of voltage and current
Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, incremental desired value
specification, desired value via BCD)
Automatic voltage regulation with linear or integral delay time T1 and
with delay time T2
Parallel operation
Line drop compensation
Status of the motor-drive unit (motor protective switch, motor is running)
Bandwidth monitoring
Function monitoring
Web-based visualization
SCADA
IEC 60870-5-104
IEC 61850 (edition 1 and edition 2)
Modbus (TCP)
DNP3 (TCP)
4.4 Operating modes
You can operate the device in the operating modes listed below. You can
select the operating mode using the keys on the connected ECOTAP VPD
CONTROL control unit.
Auto mode (AVR AUTO)
In auto mode, the ECOTAP VPD CONTROL control unit regulates voltage
automatically in accordance with the set parameters. It is not possible to per-
form manual tap-change operations using operating controls, inputs or a
control system.
Manual mode (AVR MANUAL)
In manual mode, you can perform manual tap-change operations to increase
or decrease the voltage using the keys on the ECOTAP VPD CONTROL
control unit. There is no automatic voltage regulation.