Control
65
FIGHTER 1330
Menu 6.5.0 Pool settings
Shows the current pool temperature on the sensor
(PTG). Pressing the enter button takes you to sub-
menus for the Pool settings. Only shown when pool
is selected in menu 9.1.5.
Menu 6.5.1 Start temp. pool
Here you select at which pool temperature on the
sensor (PTG) heating should start. The value is
adjustable between 5 and 60 °C in increments of
0.5 °C. The factory setting is 22.0 °C.
Menu 6.5.2 Stop temp. pool
Here you select at which pool temperature on
the sensor (PTG) heating should stop. Adjustable
between 5 and 60 °C in increments of 0.5 °C. The
factory setting is 24.0 °C.
Menu 6.5.3 Periodtime heat/pool
The length of time is set here. The value is adjust-
able between 10 and 1000 minutes. The factory
setting is 100 minutes.
Menu 6.5.4 Max-Time heatproduct
Here you select how much time of the period time
(menu 6.5.3) is to be used to heat the house when
there is a need of heating and pool heating. The
value is adjustable between 0 and 1000 minutes.
The factory setting is 50 minutes.
Menu 6.5.5 Max compr. to pool
The maximum number of compressors that can be
operated towards the pool exchanger (VX-P) is set
here. The number of compressors that currently
produce pool heat is within brackets. The value can
be adjusted between 0 and 18. Factory setting is 1.
Menu 6.5.6 Return
Pressing the enter button returns you to menu
6.5.0.
6.0 External units*
U
U
U
U
U
U
N
* Only shown when the accessory in question is
connected and activated in menu 9.1.x.
Menu 6.4.10 Periodtime shunt
The time period for the shunt (SV-K) is chosen
here. djustable between 1 and 500 seconds. The
factory setting is 5 °C
Menu 6.4.11 Shunt intensificat.
The amplification for the shunt (SV-K) is chosen
here. For example, a 2 degree difference between
the flow line and the calculated flow line with 5 in
amplification gives 10 secs/min controlling the
shunt. The value can be set between 1 and 10. The
factory setting is 1.
Menu 6.4.12 Time betw. heat cold
The time the heat pump must wait between pro-
duction of heat cooling is set here. The value can
be set between 0 and 10 hours. The factory setting
is 3 hours.
Menu 6.4.13 Return
Pressing the enter button returns you to menu
6.4.0.