Installation
3‐6
P/N 397189E
E 2006 Nordson Corporation
BM200_EASY_GEAR
Interface XS2
The interface serves as a connection between the system and external
devices. The functions are described in detail in the manual Control System
CS 20 for Bulk Melters, section Central Module with Digital Input/Output.
NOTE: It is essential to bridge Pin 9 with Pin 1 (24 V
DC
) before initial startup.
Also refer to plug connection diagram Interface XS2 for BM 20 (wiring
diagram).
NOTE: To conform with a European standard regarding electro‐magnetic
compatibility, only shielded cable may be connected. The shield
must be
connected to ground in compliance with the standard (PE connection in plug
connector).
NOTE: Inductive loads (e.g. solenoid valves) connected to the system must
be equipped with a protective device (e.g. recovery diode) that disables the
inductive voltage generated when an inductive load is switched off.
Pin Input Output Function
1 ‐ 24 V
DC
Internal switching voltage for activating inputs 2, 3, 4, 5, 7 and 9.
The switching voltage must be connected to the appropriate input.
2 24 V
DC
‐ Unit release (main contactor)
3 24 V
DC
‐ Release Drives
4 24 V
DC
‐ Switch on/off Temperature setback
5 24 V
DC
‐ Release Motor for application 1
6 - ‐ Not assigned
7 24 V
DC
‐ Release Motor for application 2
8 ‐ ‐ Not assigned
9 ‐ ‐ Internal link
10 ‐ ‐ Internal link
11 ‐ ‐ Not assigned
12 ‐ ‐ Internal link
13‐16 ‐ ‐ Not assigned
17 24 V
DC
external
‐ External potential for outputs 18, 19, 20, 21, 24 and 26
24 V
DC
+/‐ 10 %
18 ‐ 24 V
DC
max. 2 A Indication Ready for operation
19 ‐ 24 V
DC
max. 2 A Indication Collective fault
20 ‐ 24 V
DC
max. 2 A Indication Drum almost empty
21 ‐ 24 V
DC
max. 2 A Indication Drum empty
22 ‐ ‐ Internal link
23 ‐ ‐ Not assigned
24 ‐ 24 V
DC
max. 2 A Valve control application 1
25 ‐ ‐ Not assigned
26 ‐ 24 V
DC
max. 2 A Valve control application 2
27‐32 ‐ ‐ Not assigned
PE ‐ ‐ Shield
NOTE: Refer to Wiring Diagram for electrical connection.