2. Installation
Installing a RTM-8F Module
36
 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Connections & Components
Components on the RTM-8F board:
Figure 15  RTM-8F Components
Notes:
1. Zone Relay Contact Ratings:
• Maximum Switched Power is 170W or 1800 VA
• Maximum Switched Current is 6 amps
• Maximum Switched Voltage is 30 VDC or 300 VAC
• UL Rating is 6 amps @ 28 VDC or 120/300 VAC
1/8 HP @ 120/240 VAC (100,000 CYC)
1.5/0.8 A @ 120/240 VAC
Pilot Duty is 30,000 CYC
• Contact Material is Silver Nickel, Gold Plated
2. Polarity Reversal Output: 24 VDC (nominal), 18.5 mA maximum rated current. Internal Resistance: 
1,200 ohms (nominal). Intended for connection to the polarity reversal circuit of a remote station 
receiving circuit (such as the Fire•Lite RS-82 Receiving Station) having compatible ratings. The 
RTM-8F is not suitable for separate transmission of both alarm and trouble signals simultaneously to 
a remote station. Output is power-limited and wiring can leave the building.
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
Power
Limited
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Relay Disconnect LED (yellow)
Transmitter Disconnect LED (yellow)
Transmitter Output
(–) normal
(+) normal
J1 (on back of circuit board)
Relay Disconnect Switch
Transmitter Disconnect Switch
Disconnect 
Switch Settings
Disconnected
Normal
JP2 - Jumper Settings:
Alarm/Trouble Polarity 
Reversal - Remote 
Station (Power-limited)
Alarm Only Polarity 
Reversal - Remote Station 
(Power-limited)
Local Energy Municipal Box
(Nonpower-limited)
Local Energy Municipal 
Box Trouble LED (yellow)
JP1 - Cut for Polarity Reversal 
Remote Station operation
Note: If relays 
are used as 
power-limited 
circuits, paste 
supplied label to 
terminal block as 
indicated.
RTM-8Fcomp.cdr