Program Change – Level One 3. Programming
 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
47
To load the addressable device's program into memory at any time, press the 
ENTER
 key. After pressing 
the 
ENTER
 key, autoprogram displays the next new detector. If a detector was previously entered into 
memory, but is missing (no answer), the LCD display shows the following:  
If the 
ENTER
 key is pressed, the device is deleted from memory and autoprogram displays the next new 
device. If the left arrow is pressed, the program is unchanged and the next new device is displayed.
After all new detectors are presented for editing, the autoprogram feature displays the modules on the 
SLC starting with the device found at the lowest address.
Monitor Modules
This program is similar to the New Detector Autoprogram. When a new monitor module is presented, a 
typical display might be:  
The major program editing for monitor modules is the selection of the Type Code on the first line. To 
change this selection, use the up and down arrow keys as the entire field blinks. The default selection is 
monitor as shown in the screen above. Note that selection of a Type Code may change the functional 
operation of the addressable device as shown below.  
Table  5  Monitor Module Type Codes
Follow the same procedure as described in New Detectors section, for editing of the ADJ and NOUN 
fields. The default zone selection is Z00 (main circuit board NAC outputs 1 and 2) and may be set to 
Z01 through Z56 if desired. See "Appendix C: Software Zones" on page 80.
The ADJ field for monitor modules can also be used to associate a second zone as described in "New 
Detectors" on page 45. 
Type Code Label Special Function
MONITOR
none (default)
PULL
 
BOX
none
HEAT
 
DET
none
SMOKE
 
ZON
 none
WATERFLOW
causes a nonsilenceable alarm
SUPERVISY
becomes supervisory point (see Section 4, 
Operation)
AUTO
 
SUPV
becomes supervisory point 
(nonlatching 
supervisory)
TAMPLER
_
SW
becomes supervisory point (see Section 4, 
Operation)
_________ none (blank label for use when no other 
Type Code applies)
ACK
_
SW
___ functions like the 
ACKNOWLEDGE
 switch
SILENC
 
SW
functions like the 
SILENCE
 switch
RESET
 
SW
functions like the 
RESET
 switch
DRILL
___ functions like the 
DRILL
 switch
PROGRA SMOKE DET P01
NO ANSWER  DELETE
PROGRM MONITOR   M01
<ADJ>  <NOUN>    Z00