NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM
116
Control Serial Port “RS232”
Connector ......................................................RJ45 Female
Supported Signals .........................................TXD, RXD, RTS, CTS, DTR, DSR
Baud Rate......................................................max 115,200 bps
Data Format...................................................8 bits
Parity..............................................................odd, even or no parity
Stop Bits ........................................................1, 2 stop bits
ESD Protection ..............................................IEC1000-4-2
USB-Serial Port “Console”
Connector ......................................................USB Type B Female
Supported Signals .........................................D+ ,D-
Baud Rate......................................................max 115,200 bps
Data Format...................................................8 bits
Parity..............................................................no parity
Stop Bits ........................................................1 stop bits
ESD Protection ..............................................IEC1000-4-2
Auxiliary Power Port
Connector ......................................................Detachable terminal block-plug-in, 1x2 contacts
Wire Range....................................................16-26 AWG
Voltage Output...............................................12VDC+/-10%
Current Output...............................................150mA
ESD Protection ..............................................IEC 61000-4-2
Fuse Protection..............................................Resetable poly fuse – 200mA hold, 400mA trip; 30VDC max.
Ethernet Port
Connector ......................................................RJ45 Female
Connection Speed .........................................10/100 Base-T
Security..........................................................SSL
Supported Protocols ......................................http, https, Telnet,SSH
Back-Up Battery
Type...............................................................Rechargeable Sealed Lead-Acid Battery
Voltage, Current Rating .................................12VDC, 2.9Ahrs
Battery Operational Time...............................1 hr, fully loaded; 30 min. after ‘Low Bat’ LED illuminates
Battery Charging Time...................................32 hrs (from fully discharged to fully charged).
Replaceable...................................................Yes – can be replaced by authorized personnel only (NTI)
General Specifications
Power Input....................................................110/220VAC, 50 – 60 Hz, 45W
Operating Temperature..................................32° -104°F (0-40˚C)
Operating Humidity ........................................17-90%RH, non-condensing
MTBF.............................................................56,708 hours
Enclosure Size(WxDxH) ................................1 RU metal enclosure (19 x 9.5 x 1.73 inches)
TCP/IP
Supported Browsers ......................................IE, Netscape, Mozilla, Opera,Chrome
Network Configuration ...................................Allows Static or Dynamic IP Configuration
Max Number of Email Addresses ..................17; 1 per User Account + 1 for Administrator

Table of Contents

Other manuals for NTI ENVIROMUX-16D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NTI ENVIROMUX-16D and is the answer not in the manual?

NTI ENVIROMUX-16D Specifications

General IconGeneral
BrandNTI
ModelENVIROMUX-16D
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals