Group Settings Description
Group Assign the device IP to any or all groups 1 -8 (see also page 38)
Schedule Settings
Schedule Type
Always active- system will react to alert condition at all hours of each day
Active during defined times- system will only react to alert condition during times as
outlined below
Start Day First day of the week the system should react to alert condition
End Day Last day of the week the system should react to alert condition
Start Hour First hour of the day the system should begin reacting to alert condition
End Hour Last hour of the day the system should react to alert condition
Alert Settings
Disable Alerts Place a checkmark in the box to prevent alerts from being sent when the device’s status
changes
Note: If alerts for an IP device are disabled, the associated output action (see outputs"-
page 30) will still take place. There just won't be any alert notifications that this is
occurring. For example, this might be used to turn ON a device, such as a fan, when the
server room gets too warm, and OFF again when the temperature returns to normal. An
alert message may not be desired under these circumstances.
Note: if the user wants to disable alerts for an IP device after the device is already in
alert status, the user must either acknowledge or dismiss the alert first.
Notify Again Time Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will be
repeated
Notify on Return to Normal The user can also be notified when the IP device status has returned to normal by selecting the
"Notify when return to normal" box for a device.
Auto Acknowledge
Place a checkmark in this box to have alert notifications in the summary page return to normal
state automatically when sensor readings return to normal.
Enable Syslog Alerts Place a checkmark in this box to have alert notifications sent via Syslog messages
Enable SNMP traps Place a checkmark in this box to have alert notifications sent via SNMP traps (v2c)
Enable Email Alerts Place a checkmark in this box to have alert notifications sent via Email
Email Subject Enter the subject to be viewed when an email alert message is received
Enable SMS Alerts
Place a checkmark in this box to have alert notifications sent via SMS messages (requires a
modem)
Enable Siren Turn ON the siren when this device goes to alert (not applicable to ENVIROMUX-2D)
Enable Beacon Turn ON the beacon when this device goes to alert (not applicable to ENVIROMUX-2D)
Data Logging
Add to data log This is a check-box that lets the user decide if the data sampled should be recorded in the Data
Log.
Logging Period Enter the time period between logged measurements