3. Instructions
970
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Storing Data from the Rightmost Byte (Bits
12 to 15 of C = 8 hex)
Example: Storing the value 12345678 hex
in S+5 and S+6
Example Programming
In this example, ESATR(722) is used to overwrite the Number of Contact Operations set value in a
DRT2 Slave (I/O Terminal).
When CIO 0.00 and A202.06 (the Communications Port
Enabled Flag for port 06) are ON, EXPLT(720) writes the
Number of Contact Operations set value for input 2 in a
DRT2 Slave (I/O Terminal).
(Service Code = 10 hex,) Class ID = 08 hex, Instance ID =
02 hex, and Attribute ID = 68 hex.
In this case, the Number of Contact Operations is being set
to 500 (1F4 hex), so the service data is set to 000001F4.
78
15
56 7S+5
S+6
8
12 34
08 07
00
56 34 12
Frame
The data in the frame is in the
order 78 56 34 12.
In this case, 12345678 hex is
stored from the rightmost byte in
the order 78 56 34 12.
0.00
A202.06
S
C
@ESATR
D0
D100
Communications Port
Enabled Flag (Port 6)
10 08 02 68 F4 01 00 00
Attribute ID
Service Data:01F4Hex
Instance ID
Class ID
Service Code
Explicit message command format
Destination node address
CS1W-DRM21 DeviceNet Unit
(CPU Bus Unit with unit number 2)
ESATR(722)
instruction
CPU
Unit
Unit address 12 hex (because
the unit number is 2)
Slave (I/O Terminal)
with node address 10
Explicit
message
S: D0 0 0 0 C
S:+1 D1 0 0 0 A
S+2: D2 0 0 0 8
S+3: D3 0 0 0 2
S+4: D4 0 0 6 8
S+5: D5 0 1 F 4
S+6: D6 0 0 0 0
C: D201 8 6 1 2
C+1: D202 0 0 0 0
C+2: D203 0 0 0 0
Number of bytes of data: S+1 to S+6 = 6 words = 12 bytes = 0C hex
Slave’s node address = 10 = 0A hex
Class ID = 08 hex
Instance ID = 02 hex
Attribute ID = 68 hex
Service Data = F401 hex
Byte order = 8 hex (from rightmost byte), communications port = 6 hex
(port 6), and the DeviceNet Unit’s unit address = 12 hex
Response monitoring time = 0000 hex (2 s)
Explicit format type = 0000 hex (DeviceNet format)