3. Instructions
210
CS/CJ/NSJ Series Instructions Reference Manual (W474)
z Basic Timer Specifications
Note Timers are refreshed at different times depending on the timer number. Refer to the descriptions of individual timer
instructions for details
Note It is not possible to read the timer PVs of TIMU(541), TIMUX(556), TMUH(544), and TMUHX(557).
Item
TIM/TIMX
(550)
TIMH(015)/
TIMHX(551)
TMHH(540)/
TMHHX(552)
TIMU(541)/
TIMUX(556)
(See note 3.)
TMUH(544)/
TMUHX(557)
(See note 3.)
TTIM(087)/
TTIMX(555)
TIML(542)/
TIMLX(553)
MTIM(543)/
MTIMX(554)
Timing method
Decrementin
g
Decrementing Decrementing Decrementing Decrementing Incrementing Decrementing Incrementing
Timing units 100 ms 10 ms 1 ms 0.1 ms 0.01 ms 100 ms 100 ms 100 ms
Maximum SV
TIM: 999.9 s
TIMX:
6,553.5 s
TIMH: 99.99 s
TIMHX:
655.35 s
TMHH: 9.999 s
TMHHX:
65.535 s
TIMU:
0.9999 s
TIMUX:
6.5535 s
TMUH:
0.09999 s
TMUHX:
0.65535 s
TTIM: 999.9 s
TTIMX:
6,553.5 s
TIML:
115 days
TIMLX:
49,710 days
MTIM: 999.9 s
MTIMX:
6,553.5 s
Outputs/
instruction
11111118
Timer numbers Used Used Used Used Used Used Not used Not used
Completion
Flag refreshing
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
Timer PV
refreshing
(See note)
TIM PVs are
refreshed
when the
instruction is
executed,
after
executing all
cyclic tasks
each cycle,
or every
80 ms by
interrupt if
the cycle
time exceeds
80 ms.
TIMH(015)/TI
MHX(551) PVs
are refreshed
when the
instruction is
executed, after
executing all
cyclic tasks
each cycle,
and every 10
ms by
interrupt.
•Every 1 ms
• When the
instruction is
executed
•The PV
cannot be
read.
•The PV
cannot be
read.
When the
instruction is
executed
When the
instruction is
executed
When the
instruction is
executed
Value
after
reset
Com-
ple-
tion
Flags
OFF OFF OFF OFF OFF OFF OFF OFF
PVs SV SV SV --- 0 SV 0
Item
TIM/TIMX
(550)
TIMH(015)/
TIMHX(551)
TMHH(540)/
TMHHX(552)
TIMU(541)/
TIMUX(556)
TMUH(544)/
TMUHX(557)
TTIM(087)/
TTIMX(555)
TIML(542)/
TIMLX(553)
MTIM(543)/
MTIMX(554)
Operating mode
change
PV = 0
Completion Flag = OFF
--- ---
Power interrupt/reset
PV = 0
Completion Flag = OFF
--- ---
Execution of
CNR(545)/CNRX(547)
Binary: PV = FFFF, Completion Flag = OFF
BCD: PV = FFFF or 9999, Completion Flag = OFF
Not
applicable
Not
applicable
Operation in jumped
program section
(JMP(004)-JME(005))
Operating timers continue timing. Timer status is maintained.
Operation in inter-
locked program sec-
tion (IL(002)-ILC(003))
PV = SV
Completion Flag = OFF
Timer status
maintained.
PV = SV
Completion
Flag = OFF
Timer status
maintained.
Forced
set
Comple-
tion Flag
ON --- ---
PVs Set to 0. --- (See note.) Set to 0. --- ---
Forced
reset
Comple-
tion Flags
OFF --- ---
PVs Reset to SV. --- (See note.) Set to 0. --- ---