3. Instructions
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Data Control Instructions
3
TPO
z Using TPO(685) Alone
When CIO 0.00 is ON, TPO(685) takes the duty ratio in D10, converts the duty ratio to a time-
proportional output, and outputs the pulses to CIO 100.
In this case, the control period is 1 s and the output limit function is enabled with a lower limit 20.00%
and an upper limit of 80.00%.
0.00
TPO
D10
D0
1.00
S
C
R
D0
D1
D2
D3
D4
D5
D6
:
:
D10
0
4
0
0
0
6
D
4
1
0
7
F
1
0
0
1
Duty ratio
Parameters
Pulse output
Duty ratio input, read initial value, and enable output limit function.
Control period = 1.00 s
Output lower limit = 20.00%
Output upper limit = 80.00%
0 to 100.00%
Do not set.
Do not set.
Do not set.
0 to 2710 hex
TPO(685) takes the duty ratio in D10, converts that
duty ratio to a time-proportional output, and outputs
the pulse output to bit 00 of CIO 1.