388
PLC Comparison Charts Appendix A
Table
Data Pro-
cessing
Instruc-
tions
SET STACK SSET Yes (Four words of stack control information.
Number of words specified in binary: 5 to
65535)
No Yes (Four
words of stack
control infor-
mation. Num-
ber of words
specified in
BCD: 3 to
9999)
No
PUSH ONTO
STACK:
PUSH Yes No Yes No
FIRST IN FIRST
OUT
FIFO Yes No Yes No
LAST IN FIRST
OUT
LIFO Yes No Yes No
FIND MAXIMUM/
FIND MINIMUM
MAX,
MIN
Yes (Two words in control data field. Table
length specified in binary: 1 to FFFF)
Yes (One word in control data field. Table
length specified in BCD: 1 to 999)
DATA SEARCH SRCH Yes (Table length specified in binary: 1 to
FFFF. PLC memory address output to IR0.
Number of matches can be output to DR0.)
Ye s ( Ta b l e
length speci-
fied in BCD: 1
to 6556. PLC
memory
address out-
put to C+1.
Number of
matches can-
not be output
to DR0.)
Ye s ( Ta b l e
length speci-
fied in BCD: 1
to 9999. PLC
memory
address out-
put to IR0.
Number of
matches can-
not be output
to DR0.)
Ye s ( Ta b l e
length speci-
fied in BCD: 1
to 6556. PLC
memory
address out-
put to C+1.
Number of
matches can-
not be output
to DR0.)
FRAME CHECK-
SUM
FCS Yes Yes No Yes
SUM SUM Yes (Same as C200HX/HG/HE: Sum possi-
ble for bytes as well as words.)
Yes (Sum pos-
sible for bytes
as well as
words.)
Yes (Sum pos-
sible for words
only.)
Yes (Sum pos-
sible for bytes
as well as
words.)
SWAP BYTES SWAP Yes (Can be used for data communications
and other applications.)
No No No
DIMENSION
RECORD
TABLE:
DIM Yes No No No
SET RECORD
LOCATION
SETR Yes No No No
GET RECORD
LOCATION
GETRYes NoNoNo
Data Con-
trol
Instruc-
tions
SCALING SCL Yes Yes No Yes
SCALING 2 SCL2 Yes No No Yes
SCALING 3 SCL3 Yes No No Yes
PID CONTROL PID Yes (Output can be switched between 0%
and 50% when PV = SV. PID and sampling
period specified in binary.)
Yes (PID and
sampling
period speci-
fied in BCD)
Yes (PID and
sampling
period speci-
fied in BCD)
(*1)
Yes (PID and
sampling
period speci-
fied in BCD)
PID CONTROL
WITH AUTO-
TUNIG
PIDAT Yes No No No
LIMIT CONTROL LMT Yes No Yes (*1) No
DEAD BAND
CONTROL
BAND Yes No Yes (*1) No
DEAD ZONE
CONTROL
ZONE Yes No Yes (*1) No
TIME-PROPOR-
TIONAL OUT-
PUT
TPO Yes (*6) No No No
AVERAGE AVG Yes (Number of scans specified in binary) Yes (Number
of scans spec-
ified in BCD)
No Yes (Number
of scans spec-
ified in BCD)
Item Mne-
monic
CJ1-H/CJ1M Series CS1-H
Series
C200HX/HG/
HE
CVM1/CV
Series
CQM1H
CJ1-H-R CJ1-H CJ1-M