EasyManuals Logo

Omron CJ2M-CPU Series User Manual

Omron CJ2M-CPU Series
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #249 background imageLoading...
Page #249 background image
8-89
8 Pulse Outputs
CJ2M CPU Unit Pulse I/O Module User’s Manual
8-11 Pulse Output Patterns
8
The following operations can be performed in Independent Mode by combining instructions.
8-11-2 Positioning Control (Independent Mode)
Starting Pulse Output
Operation
Example
application
Frequency changes Function
Procedure
Instruc-
tions
Settings
Outputting
the specified
speed
Positioning
without accel-
eration or
deceleration
Starts outputting
pulses at the speci-
fied frequency and
stops immediately
when the specified
number of pulses
has been output.
The target position
(specified number of
pulses) cannot be
changed during
positioning.
PULS
SPED
(Indepen-
dent)
Number of
pulses
Relative or
absolute
pulse speci-
fication
•Port
•Pulse +
direction
Independent
Target fre-
quency
Simple trape-
zoidal control
Positioning
with trapezoi-
dal accelera-
tion and
deceleration
(Same rate
used for accel-
eration and
deceleration;
no starting
speed).
The number of
pulses cannot
be changed
during posi-
tioning.
Accelerates and
decelerates at the
same fixed rate and
stops immediately
when the specified
number of pulses
has been output.*
PULS
ACC
(Indepen-
dent)
Number of
pulses
Relative or
absolute
pulse speci-
fication
•Port
•Pulse +
direction
Independent
Accelera-
tion and
decelera-
tion rate
Target fre-
quency
Complex
trapezoidal
control
Positioning
with trapezoi-
dal accelera-
tion and
deceleration
(Separate
rates used for
acceleration
and decelera-
tion; starting
speed)
The number of
pulses can be
changed dur-
ing position-
ing.
Accelerates and
decelerates at a
fixed rates. The
pulse output is
stopped when the
specified number of
pulses has been
output.*
The target position
(specified number of
pulses) can be
changed during
positioning.
PLS2 Number of
pulses
Relative or
absolute
pulse speci-
fication
•Port
•Pulse +
direction
Accelera-
tion rate
Decelera-
tion rate
Target fre-
quency
Starting fre-
quency
Pulse frequency
Target
frequency
SPED instruction
executed
Time
Specified number of pulses
(Specified with PULS)
Outputs the specified number
of pulses and then stops.
Time
Pulse frequency
Target
frequency
Acceleration/
deceleration rate
Specified number of pulses
(Specified with PULS)
Outputs the specified
number of pulses and
then stops.
ACC instruction
executed.
PLS2
instruction
executed.
Time
Acceleration
rate
Target
frequency
Starting
frequency
Deceleration rate
Specified number of pulses
Target
frequency reached
Deceleration point
Output stops
Stop frequency
Pulse
frequency

Table of Contents

Other manuals for Omron CJ2M-CPU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2M-CPU Series and is the answer not in the manual?

Omron CJ2M-CPU Series Specifications

General IconGeneral
Power Supply24 VDC
Number of InstructionsOver 400 instructions
ModelCJ2M-CPU11, CJ2M-CPU12, CJ2M-CPU13, CJ2M-CPU14, CJ2M-CPU15
Program Capacity5K steps to 60K steps
I/O CapacityUp to 2, 560 points
Communication PortsEthernet, USB, RS-232C
Execution Time0.04 µs per basic instruction
Operating Temperature0 to 55°C
Position ControlSupported
High-speed Counter100 kHz max.
Pulse Output100 kHz max.
Maximum Units40 units
Storage Temperature-20 to 75°C
Interrupt InputsSupported

Related product manuals