Omron CS1W-PRM21 - Master Status 2 Word

Omron CS1W-PRM21
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
139
Troubleshooting Using Error Status
Section 7-4
7-4-2 Master Status 2 Word
The Master Status 2 Word (CIO Word n+6) contains error indications on the
PROFIBUS interface and network. The figure below shows the Master Status
2 Word layout. The corresponding bit flag will turn ON if an error event has
occurred.
Note n = CIO 1500 + (25 x unit number).
09 File read error An error has occurred, when loading the configuration from the non-volatile mem-
ory to the volatile memory at start up. Most likely cause is a failure or interruption
during the writing process.
Most likely causes:
A failure or interruption during the writing process.
A failure during the reading process.
A faulty Memory Card.
To correct this:
Check the Memory Card for faults.
Restart the PLC Unit, to re-download the configuration.
If the problem persists, use CX-Profibus to re-download the configuration.
If the problem persists, replace the PROFIBUS-DP Master unit.
13 Error Log storage error An error has occurred, when writing the error log to the non-volatile memory, or
when reading the error log from non-volatile memory during start up.
Most likely causes: A failure or interruption during the writing process.
To correct this:
Send an ERROR LOG CLEAR FINS command to the Unit.
Restart the Unit.
If the problem persists, replace the PROFIBUS-DP Master unit.
1514131211109876543210
Word n+6
Disturbed bus error
PROFIBUS protocol error
Double Master address error
Hardware error
Mode command error
Parameter error
Bit Name Description / Correction
00 Disturbed bus Error An error has occurred in the PROFIBUS interface, with distorted messages
received by the PROFIBUS-DP Master Unit.
Most likely causes:
No or invalid termination or no inductors used at high baud rates.
Faulty wiring.
To correct this:
Check the termination on the appropriate stations.
Restart the PLC Unit, to re-download the configuration.
If the problem persists, use CX-Profibus to re-download the configuration.
If the problem persists, replace the PROFIBUS-DP Master unit.