CHAPTER 5 PARAMETERS
E5CK
5–38
Operation at power ON
Selects one of the following operations when the power is turned ON:
Ă• Continue" : Starts operations from the state that was active when the power was
interrupted.
Ă• Reset" : Resets the controller.
Ă• Run" : Starts normal program operation.
Ă• Manual" : Sets the controller to the manual mode.
Manual" cannot be selected when Auto/Manual key operation is protected.
Setting Range
Default
“ ” :Continue/ “ ” :Reset/ “ ” Run/ “ ” :Manual
ĂRelated description
4.6 Setting Running Conditions/Operation at power ON (page 4Ć14)
End condition
Ă• Specifies a reset state or continued control on the SP of the final step after program
operation ends.
Ă• The program end state will not change when the number of steps" parameter setting
has been changed after program operation ends. However, when control on the SP
is continued, the SP of the final step is selected after the number of steps has been
changed.
Setting Range
Default
“ ” :Reset/ “ ” :Continued control using final SP
ĂRelated description
4.6 Setting Running Conditions/End condition (page 4Ć15)
ĂRelated parameter
Number of steps" (program mode)
Note: The end of operation does not refer to the end of the pattern. It refers to the end
of executing the pattern the specified number of times.