EasyManua.ls Logo

Omron E5GN - Page 72

Omron E5GN
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E5GN
55
PV
The additional PV display parameter must
be set to ON.
The process value is displayed on the No.1 display, and nothing is displayed (blank)
on the No.2 display.
Monitor Range Unit
Process
Value
Input range lower limit -10%FS to input range upper limit +10%FS
Scaling lower limit -10%FS to scaling upper limit +10%FS
EU
The decimal point position is dependent on the selected sensor.
FĂRelated parameters
Input type" (initial setting level)
Set point upper limit" Set point lower limit" (initial setting level)
PV/SP
The process value is displayed on the No.1 display, and the set point is displayed on
the No.2 display.
Monitor Range Unit
Process
Value
Input range lower limit -10%FS to input range upper limit +10%FS
Scaling lower limit -10%FS to scaling upper limit +10%FS
EU
Set Point Set point lower limit to set point upper limit EU
The decimal point position is dependent on the selected sensor.
Refer to the PV parameter.
Multi-SP (set point 0 to 3)
The multi-SP uses parameter must be set to
ON.
MultiĆSP allows you to set up to four set points (SP 0 to 3) in adjustment level. These
can be switched by operating the keys on the front panel. In the parameter, enter set
points 0 to 3.
Ă MultiĆSP can also be selected by communications.
Operation Level
Function
Monitor
See
Function
Monitor
See
Function
See

Table of Contents

Other manuals for Omron E5GN

Related product manuals