EVOHD+ Installation Guide
Display Entry Delay Timer
SECTION [003]: OPTION [3]
Option [3] OFF=Will not display the Entry Delay Timer (default)
Option [3] ON=LCD screen will display Entry Delay Timer
Confidential Mode
SECTION [003]: OPTIONS [4] AND [5]
Section [003]:
Option [4] OFF=Normal Mode (default)
Option [4] ON=Confidential Mode
Option [5] OFF=LCD screen activated by entering an access code (default)
Option [5] ON=LCD screen activated by pressing a button
Confidential Mode Timer
SECTION [007]
Section [007] determines the amount of time without action before the keypad enters Confidential Mode. The Confidential Mode Timer can be set from 005
seconds to 255 seconds. Default: 120 secs.
Time Display Option
SECTION [003]: OPTION [8]
Option [8] OFF=Date displayed as yy/mm/dd (default)
Option [8] ON=Date displayed as dd/mm/yy
Muting
SECTION [004]: OPTION [1]
Option [1] OFF=Audible sounds (default)
Option [1] ON=Mute
Beep on Exit Delay
SECTION [004]: OPTION [2]
Option [2] OFF=Exit Delay beep disabled
Option [2] ON=Exit Delay beep enabled (default)
Chime on Zone Closure
SECTION [004]: OPTION [4]
Option [4] OFF=Chime on Zone Closure disabled (default)
Option [4] ON=Chime on Zone Closure enabled
Beep on Trouble
SECTION [005]: OPTIONS [1] TO [4]
O
ption [1] OFF=Beep disabled: System Troubles and Clock Loss
Option [1] ON=Beep enabled: System Troubles and Clock Loss
Option [2] OFF=Beep disabled: Communicator Troubles
Option [2] ON=Beep enabled: Communicator Troubles
Option [3] OFF=Beep disabled: Module and Digiplex bus Troubles
Option [3] ON=Beep enabled: Module and Digiplex bus Troubles
Option [4] OFF=Beep disabled: all Zone Troubles
Option [4] ON=Beep enabled: all Zone Troubles
Keypad Tamper Enable
SECTION [006]: OPTION [5]
Option [5] OFF=Keypad's tamper is disabled (default)
Option [5] ON=Keypad's tamper is enabled
Time Format
SECTION [005]: OPTION [7]
Option [7] OFF=Time uses the International time format (default).
Option [7] ON=Time uses the US time format.
Digiplex bus
Voltmeter
1. From Normal Mode press and hold the [0] key.
2. Enter the [
INSTALLER CODE] (by default 000000).
3. Press [
ACC].
NOTE: The voltage may drop during the control panel battery test.