Loading...
890SD Standalone Drive
Page 5-38 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
SET-UP PARAMETERS
PREF 6511/6901
Display
Default Brief Description V/Hz
SV Vector
Required parameters for each control mode are shown shaded.
71.03
ENCODER
INVERT
0 : FALSE
1 : TRUE
Encoder direction :-
when TRUE, changes
the sign of the
measured speed and
the direction of the
position count.
x
x x 27.06
MAG CURRENT
product code dependent
Enter the No-Load
Amps from the motor
nameplate
x
(enter for a
Stationary
Autotune)
1.03
A1N1 TYPE
0 : -10..+10 V
1 : 0..+10 V
Select the input range
and type
x x x
2.03
AIN2 TYPE
0 : -10..+10 V
1 : 0..+10 V
Select the input range
and type
x x x
3.03
AIN3 TYPE
0 : -10..+10 V
1 : 0..+10 V
2 : 0..20 mA
3 : 4..20 mA
Select the input range
and type
x x x