DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
DOC-0017-03-EN-B 04.04.2023 101 (125)
Drive Type: 3ø, Fundamental Voltage = 230V
Line Inductance = 84µH, PSCC = 5kA
The 2.2kW Frame 2 is designated as “Professional Equipment” as defined in EN61000-3-2.
Frame Size:
2
3
4
Product Code:
15G-32-0100...
15G-33-0170...
15G-34-0210...
Power Rating (kW):
2.2
4
5.5
Current Rating (A):
10
17
21
Harmonic No.
RMS Current (A)
1
9.21
16.09
20.04
3
0.01
0.01
0.01
5
4.07
5.40
6.08
7
1.22
0.35
0.42
9
0.01
0.01
0.01
11
0.80
1.33
1.53
13
0.33
0.20
0.49
15
0.00
0.01
0.01
17
0.34
0.62
0.68
19
0.13
0.22
0.39
21
0.00
0.01
0.01
23
0.19
0.35
0.34
25
0.06
0.19
0.28
27
0.00
0.01
0.01
29
0.12
0.21
0.16
31
0.03
0.16
0.19
33
0.00
0.01
0.01
35
0.09
0.12
0.06
37
0.02
0.12
0.12
39
0.00
0.01
0.01
40
0.00
0.00
0.00
Total RMS Current (A):
10.19
17.50
21.02
THD: Current (%):
47.36
35.01
31.80

Table of Contents