DOC-0017-03-EN: AC15 Series - Hardware Installation Manual     
20 (125)  DOC-0017-03-EN-B   04.04.2023  
6.2  Electrical 
Please ensure that you have read and are familiar with the ‘Safety’ 
chapter before proceeding with the electrical installation. 
 
 
RISK OF ELECTRIC SHOCK 
 
Terminal covers, main covers, and cover fixings must remain in place 
while the drive is energised. 
These should only ever be removed once the supply to the unit and/or 
system has been disconnected, and the residual energy in the DC link 
capacitors has been discharged. 
 
-  All activities covered in this chapter should be carried out when there is no power to the 
inverter.  
-  If the drive has been powered up, ensure enough time has elapsed that the inverter has 
discharged its residual energy.  
-  Always check that the voltages on the user terminals are at a safe level (<50V) before 
carrying out any of these activities. 
 
-  STO always overrides any attempt to start the inverter. If one or both STO control inputs is 
requesting the STO function, the inverter will not start.  
-  Refer to ‘Chapter 8: Safe Torque Off (STO): SIL2, PLd’ for further information. 
 
 
 Power Stack Wiring 
Terminal Identification  
Frame 1: 
 
 
 
Supply Input Phase L3 / Protective Earth 
Supply Input Phase L2 / Neutral 
Supply Input Phase L1 / Live 
DC+ / Dynamic Brake Resistor Connection (+) 
Dynamic Brake Resistor Connection (-)