5-84
Zone AttributesTable 17:
Attribute Description
Output Pattern
Default = Constant
•y
•y
Constant 24VDC
ANSI .5 sec on, .5 sec off, .5 sec on, .5 sec off, 5 sec on, 1.5 sec off
March Code 60 signals per minute
Double Time 120 signals per minute
Day Sensitivity
Default = 3.5%
3.5% default
•y obscuration
•y
Night Sensitivity
Default = 2.5%
2.5% default
•y obscuration
•y
i.e., weekends, Holidays.
Heat Sensitivity
Default = 135
Range: 135
Fixed/ROR Heat Sensitivity
increase in 1 minute
Default = 135F
Range: 135
Auto-Silence Timer
Default = 0 minutes
Auto-Unsilence Timer
Default = 0 minutes
Silence-Inhibit Timer
Default = 0 minutes
not
Restore Delay
Default = 0 minutes