3-26
Notication Appliance Circuits Installation
(Please refer to the Class A and B wiring examples located in this section.)
NAC Wiring
y
y
y
“NAC Compatibility Document”, Potter #5403592
y
NAC Maximum Wiring Impedance Formula
functionload
(Alarm Current of Notication Appliances) x (Wire Resistance) < 3 Volts
NAC Wiring Congurations
NAC Class B Wiring Example Figure 23.
Notes:
1.
2.
DWG #602-4
NAC 1 NAC 2
- + - +
NAC 3 NAC 4
- + - +
NAC 5 NAC 6
- + - +
5.1k EOL
Potter Part #3005013
Notification
Appliance