DESCRIPTION OF PROGRAMMING PARAMETERS
The comparator source can be set according
to the following table:
There is no source for the
comparator
Voltage analog input 1 will
be used as source by the
comparator.
Voltage analog input 2 will
be used as source by the
comparator.
Current analog input 2 will
be used as source by the
comparator.
Pulse input will be used
as source by the
comparator.
Output
activation level
comparator
mode
Define the level to compare with the source
selected in parameter Ad.66. In case this
level is over passed, one of the digital outputs
adjusted as 34 ‘COMPARAT’ will enable it.
See parameters OU.31 to OU.33.
Output
deactivation
level
comparator
mode
Define the level to compare with the source
selected in parameter Ad.66. In case this
level is over passed, one of the digital outputs
adjusted as 34 ‘COMPARAT’ will disable it.
See parameters OU.31 a OU.33.
Always
Enable
DI
Depende
nt
Configure safe operation mode. With it, the
drive operates if it has permissions to do so.
The drive responds to
any start command
without requiring further
permissions.
The drive will only
operate if the digital
input configured as ‘13
RUNEnable’ is active.