DESCRIPTION OF PROGRAMMING PARAMETERS
195
Group 9: Protections Pr
Screen
Description
Default
value
Range
Function
Set on
RUN
Pr.4
Load duty type
Heavy
NRML
HEAVY
Select the load type.
OPT.
DESCR.
FUNCTION
0
NRML
Selects the normal load
type (variable torque) for
applications such as fans
or pumps.
1
HEAVY
Selects the heavy load
type (constant torque) for
applications such as
elevators and cranes.
NO
Pr.5
Phase loss
type
NONE
0 to 4
Select phase loss protection type.
OPT.
DESCR.
FUNCTION
0
NONE
Phase loss protection
disabled.
1
OUTPUT
Output phase loss
protection enabled.
2
INPUT
Input phase loss
protection enabled. For
its correct operation, the
user should set the
parameter Pr.6.
3
ALL
Input and output phase
loss protection enabled.
For its correct operation,
set the parameter Pr.6.
Caution: Users should ensure that
disabling this protection does not
compromise the operation of the installation
and/or equipment.
NO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD300 Series and is the answer not in the manual?

Power Electronics SD300 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD300 Series
CategoryInverter
LanguageEnglish

Related product manuals